Join our Mailing List    

Your ultimate source for explosion-proof air conditioners, building pressurization units, gas phase filtration systems, and fully integrated wall, pad and split system hazardous and industrial climate control solutions!
Products Services Contacts Us About Us
News      Testimonials
Introduction
Product Applications
Unit Case Styles & Materials
Unit Configurations
Standard Features
Optional Features
Specs, Certification & Warranty
Unit Accessories
Technical Bulletins
Model Number Matrix
On-Line Inquiries
Unit Size Calculator Tool

Harsh Duty Enclosure & Cabinet Air Conditioners

Model EAC
Enclosure
Air Conditioners

Unit Accessories

explosion proof ETL listed electrical and electronic enclosure and cabinet air conditioners for hazardous classified  areas and locations

Gas Detection Systems

Bebco provides these accessories to achieve the ultimate level of safety when Model EAC Units are fitted on enclosures
containing analyzers or other processing equipment that requires hydrocarbon gas, H2S gas or O2 deficiency monitoring.

These systems can be integrated easily and come with all necessary components to detect critical
hazards and warn your facility’s safety personnel of potentially catastrophic conditions.

Bebco provides all necessary accessories to complete your installation easily!

Hazardous Location Enclosure Air Conditioner Gas Detection Systems
Click this image to learn more!
Model CGDM, HGDM, OGDM & GDPS
Monitors, Matching Sensors & Power Supplies
Provides detection of hydrocarbons, H2S or O2 deficiency!


 
 

 
 

 
 







 


Hydrocarbon Monitor:
 
 
H2S Monitor:
 
 
O2 Monitor:
 
 
Response/ Op Temp:
Housing Ratings:
Housing Dimensions:
Sensor Dimensions:
Power Requirements:
Signal Output:
Alarm Contacts:


Conduit Ports:
Certification:

Catalytic Bead Adsorption - 0-100% LEL
Accuracy & Repeatability: +/- 5% Full Scale
Zero Drift: < 5% per Year
Metal Oxide Adsorption - 0-100 PPM
Accuracy & Repeatability: +/- 5% Full Scale
Zero Drift: < 2% per Year
Electrochemical Fuel Cell - 0-26%
Accuracy & Repeatability: +/- 2% Full Scale
Zero Drift: < 2% per Month
90% < 30 Seconds / -40° to 175° F
NEMA 7, Class 1, Division 1, Group C & D
5.5" H x 5.3" W x 4.0" D (GDPS is 6.0" D)
3.0" H x 2.0" Diameter
Monitor: 22-28 VDC / Power Supply: 120 VAC
4-20ma VDC, Linear
Low & High Set Points & Fault Supervision
Form C 0.5 amps @ 125 VAC or 30 VDC
Programmed to open or close on alarm
3/4" Top & Bottom Sides
UL Listed
Open this Accessory’s Technical Bulletin in a separate window!


Bebco Environmental Controls Corporation
Physical Address: 4725 Lawndale Street, La Marque, Texas 77568
Mailing Address: P.O. Box 68 Hitchcock, Texas 77563
Phone: (844) 397-4822     |   Fax: (409) 935-5819
Office Hours:
 8 AM to 5 PM CST, Monday - Friday
Please visit this site for NFPA 496 UL Classified Enclosure Purging Systems:
Best Purging Systems Corporation

  |     |     |  
Terms of Use   |     |   Privacy Policy   |   Terms of Sale
Product Warranties   |   Return Policy & Form   |   Product Registration Form   |   Site Map

Copyright © 2019 – All Rights Reserved      Click the Terms of Use Link above for more information.